PRODUCTS CENTER
Laos 40.5kV 1250A
Category:
Product Description
According to standards and scope of application
1. This product meets the following standards:
IEC62271-102 AC High Voltage Disconnector and Earthing Switch
GB/T 11022-1999 Common Technical Requirements for Standards of High-voltage Switchgear and Control Equipment
GB 1985-2004 High-voltage AC Disconnectors and Earthing Switches
GB 50150 Electrical equipment handover test standard for electrical equipment installation engineering
Technical Conditions for Ordering of DL/T 486 AC High-voltage Disconnectors and Earthing Switches
Common technical requirements for DL/T 593 standards for high-voltage switchgear and controlgear
2. This product is a three-phase AC frequency 50Hz/60Hz outdoor high-voltage transmission equipment, for no-load conditions to disconnect or connect high-voltage lines, in order to high-voltage lines for switching, change the mode of operation, as well as the maintenance of the bus and circuit breakers and other high-voltage electrical equipment to implement safe electrical isolation.
Use of environmental conditions
|
1. Ambient temperature:-40 ℃ ~ 55 ℃ |
|
2. Altitude: not more than 2000mm |
|
3. Earthquake intensity: 8 degrees and below |
|
4. Maximum wind speed: 35 m/s |
Product model meaning and its selection

|
Rated voltage |
insulating medium |
Hardware |
Product design serial number |
|
12kV
|
porcelain vase
|
hot galvanizing |
SSOD2-12 |
|
Stainless Steel |
SSOD4-12 |
||
|
Silicone rubber
|
hot galvanizing |
SSOD8-12 |
|
|
Stainless Steel |
SSOD10-12 |
||
|
Epoxy Resin
|
hot galvanizing |
SSOD14-12 |
|
|
Stainless Steel |
SSOD16-12 |
||
|
24kV
|
Silicone rubber
|
hot galvanizing |
SSOD8-24 |
|
Stainless Steel |
SSOD10-24 |
||
|
Epoxy Resin
|
hot galvanizing |
SSOD14-24 |
|
|
Stainless Steel |
SSOD16-24 |
||
|
40.5kV
|
Silicone rubber
|
hot galvanizing |
SSOD8-40.5 |
|
Stainless Steel |
SSOD10-40.5 |
||
|
Epoxy Resin
|
hot galvanizing |
SSOD14-40.5 |
|
|
Stainless Steel |
SSOD16)-40.5 |
Technical parameters
|
Rated voltage (kV) |
12 |
24 |
40.5 |
|
|
Rated current (A) |
200、400、630、1000、1250 |
|||
|
Rated frequency |
50Hz/60Hz |
|||
|
Rated lightning impulse withstand voltage
|
To the ground |
95 |
125 |
185 |
|
fracture |
110 |
145 |
215 |
|
|
Rated power frequency withstand voltage (kV)
|
To the ground |
50 |
60 |
95 |
|
fracture |
60 |
70 |
118 |
|
|
Isolation fracture distance |
≥ 200mm |
≥300mm |
≥ 450mm |
|
|
Rated short-time withstand current and duration (kA/S) |
25kA, 20kA, 16kA/4S (or 3S) |
|||
|
Rated peak withstand current |
40kA 50kA |
|||
|
Mechanical life |
3000 times |
|||
|
Creepage distance of insulator |
≥ 372mm |
≥650mm |
≥ 1085mm |
|
: next page