40.5kV 1250A
SSOD double column series outdoor column isolation switch (hereinafter referred to as isolation switch) is a hook rod operation type isolation switch, the knife has a self-locking device. This series of isolating switches is suitable for the isolation of 12 ~ 40.5kV overhead lines, and the opening and closing operations are carried out under no load. The main function is to isolate the voltage during equipment or line maintenance to ensure safe operation. Use with circuit breakers or load switches and provide a safe visible break for the line.
Key words:
40.5kV 1250A
Category:
Product Description
According to standards and scope of application
1. This product meets the following standards:
IEC62271-102 AC High Voltage Disconnector and Earthing Switch
GB/T 11022-1999 Common Technical Requirements for Standards of High-voltage Switchgear and Control Equipment
GB 1985-2004 High-voltage AC Disconnectors and Earthing Switches
GB 50150 Electrical equipment handover test standard for electrical equipment installation engineering
Technical Conditions for Ordering of DL/T 486 AC High-voltage Disconnectors and Earthing Switches
Common technical requirements for DL/T 593 standards for high-voltage switchgear and controlgear
2. This product is a three-phase AC frequency 50Hz/60Hz outdoor high-voltage transmission equipment, for no-load conditions to disconnect or connect high-voltage lines, in order to high-voltage lines for switching, change the mode of operation, as well as the maintenance of the bus and circuit breakers and other high-voltage electrical equipment to implement safe electrical isolation.
Use of environmental conditions
|
1. Ambient temperature:-40 ℃ ~ 55 ℃ |
|
2. Altitude: not more than 2000mm |
|
3. Earthquake intensity: 8 degrees and below |
|
4. Maximum wind speed: 35 m/s |
Product model meaning and its selection

|
Rated voltage |
insulating medium |
Hardware |
Product design serial number |
|
12kV
|
porcelain vase
|
hot galvanizing |
SSOD2-12 |
|
Stainless Steel |
SSOD4-12 |
||
|
Silicone rubber
|
hot galvanizing |
SSOD8-12 |
|
|
Stainless Steel |
SSOD10-12 |
||
|
Epoxy Resin
|
hot galvanizing |
SSOD14-12 |
|
|
Stainless Steel |
SSOD16-12 |
||
|
24kV
|
Silicone rubber
|
hot galvanizing |
SSOD8-24 |
|
Stainless Steel |
SSOD10-24 |
||
|
Epoxy Resin
|
hot galvanizing |
SSOD14-24 |
|
|
Stainless Steel |
SSOD16-24 |
||
|
40.5kV
|
Silicone rubber
|
hot galvanizing |
SSOD8-40.5 |
|
Stainless Steel |
SSOD10-40.5 |
||
|
Epoxy Resin
|
hot galvanizing |
SSOD14-40.5 |
|
|
Stainless Steel |
SSOD16)-40.5 |
Technical parameters
|
Rated voltage (kV) |
12 |
24 |
40.5 |
|
|
Rated current (A) |
200、400、630、1000、1250 |
|||
|
Rated frequency |
50Hz/60Hz |
|||
|
Rated lightning impulse withstand voltage
|
To the ground |
95 |
125 |
185 |
|
fracture |
110 |
145 |
215 |
|
|
Rated power frequency withstand voltage (kV)
|
To the ground |
50 |
60 |
95 |
|
fracture |
60 |
70 |
118 |
|
|
Isolation fracture distance |
≥ 200mm |
≥300mm |
≥ 450mm |
|
|
Rated short-time withstand current and duration (kA/S) |
25kA, 20kA, 16kA/4S (or 3S) |
|||
|
Rated peak withstand current |
40kA 50kA |
|||
|
Mechanical life |
3000 times |
|||
|
Creepage distance of insulator |
≥ 372mm |
≥650mm |
≥ 1085mm |
|
Related Products